Page 58 - Mechanical Products Installation Handbook IH-1000M
P. 58

 50 INSTALLATION INSTRUCTIONS
Mechanical Outlets
Figure 730 Outlet Hole Diameter Guide
(3 of 3)
 Nominal Run Size ANSI Inches DN
139,7
125
6
150
Nominal Branch Size ANSI Inches DN
Hole Diameter Inches mm
 Minimum
Maximum
2.88
73,0
2.13
54,0
2.13
54,0
2.63
66,7
2.88
73,0
3.63
92,1
4.63
117,5
2.13
54,0
2.13
54,0
2.63
66,7
2.88
73,0
2.88
73,0
3.63
92,1
3.63
92,1
2.88
73,0
2.88
73,0
3.63
92,1
4.63
117,5
2.88
73,0
                      165,1
150
2-1/2 2.75
65 69,9
1-1/4 2.00
32 50,8
1-1/2 2.00
40 50,8
2 2.50
50 63,5
2-1/2 2.75
65 69,9
3 3.50
80 88,9
4 4.50
100 114,3
1-1/4 2.00
32 50,8
1-1/2 2.00
40 50,8
2 2.50
50 63,5
2-1/2 2.75
65 69,9
76,1 mm 2.75 65 69,9)
3 3.50
80 88,9
4 3.50
100 88,9
2-1/2 2.75
65 69,9
76,1 mm 2.75 65 69,9)
3 3.50
80 88,9
4 4.50
100 114,3
2-1/2 2.75
65 69,9
           8
200
216,3
200
         Note: Proper hole preparation is required for effective sealing and performance. Check the pipe seal surface within 5/8˝ of the hole to be certain it is free from conditions that would affect proper gasket sealing. Remove any sharp or rough edges from the hole or upper housing contact area that might affect assembly, proper seating of the locating collar, or flow from the outlet. Check gasket grade to be certain it is suitable for the service. For crosses, ensure double outlet holes are aligned
on opposite sides of the pipe. The use of threaded products other than steel pipe, such as dry pendants, may not be compatible with the female-threaded outlet on the Mechanical Tee. Always confirm compatibility by contacting GRINNELL Mechanical Products.




   56   57   58   59   60