Page 54 - Mechanical Products Installation Handbook IH-1000M
P. 54

 46 INSTALLATION INSTRUCTIONS Mechanical Outlets
Figure 730 Tee and Cross
• WARNING
Always read and understand the instructions including the “Installation Guidelines” provided on page 15. Failure to follow these instructions may result in improper product installation, joint failure, leakage, serious personal injury, and/or property damage.
 Pipe Preparation
Step 1. Refer to the Figure 730 Outlet Hole Diameter Guide on pages 48 through 50 to verify hole size.
Step 2. Drill the hole on the pipe center-line. For crosses, ensure double outlet holes are aligned.
Step 3. Remove any sharp or rough edges from the hole or upper housing contact area. The gasket-seating surface on the pipe should be examined to verify all loose debris, dirt, chips, paint and any other foreign material such as grease are removed.
 The following installation instructions apply to Figure 730 Mechanical Outlet Tee and Cross with threaded or grooved outlets as described in technical data sheet G210. If a cross configuration is desired, the lower housing is replaced with an upper outlet housing.
Verify that the gasket grade is correct for the application intended. Refer to Tech Data Sheet G610 for additional information.
Step 1. Check for proper gasket position- ing in the housing. The alignment tabs on the gasket should fit into the recesses of the housing. Gasket lubrication is not required on this product for applications above 40°F (4°C). For assembly or application below 40°F (4°C), a petroleum-free lubricant is recommended.
Step 2. With one nut and bolt removed, “swing around” as shown.
 Step 1.
  Step 2.





















































































   52   53   54   55   56