 380 PRESSURE & DESIGN DATA
Pressure Performance for Copper Tubing (1 of 2)
Figure 672 Rigid Coupling
  Nominal ANSI Inches DN
2
50
2-1/2
65
3
80
4
100
5
125
6
150
8
200
Nominal ANSI Inches DN
2
50
2-1/2
65
3
80
4
100
Type “K” - ASTM B 88
Type “L” - ASTM B 88
  Wall Thickness Inches mm
  Maximum Working Pressure psi bars
  Maximum End Load Lbs. kN
   Wall Thickness Inches mm
  Maximum Working Pressure psi bars
  Maximum End Load Lbs. kN
   0.083 300
2,1 20,7
0.095 300
2,4 20,7
0.109 300
2,8 20,7
0.134 300
3,4 20,7
0.160 300
4,1 20,7
0.192 300
4,9 20,7
0.271 300
6,9 20,7
1,065
4,74
1,625
7,23
2,300
10,23
4,005
17,82
6,190
27,55
8,840
39,34
15,550
69,2
0.070 300
1,8 20,7
0.080 300
2,0 20,7
0.090 300
2,3 20,7
0.110 300
2,8 20,7
0.125 300
3,2 20,7
0.140 300
3,6 20,7
0.200 300
5,1 20,7
1,065
4,74
1,625
7,23
2,300
10,23
4,005
17,82
6,190
27,55
8,840
39,34
15,550
69,2
         Type “M” - ASTM B 88
DWV - ASTM B 306
–––
–––
0.045 100 765
1.1 6,9 3.40
 Wall Thickness Inches mm
  Maximum Working Pressure psi bars
  Maximum End Load Lbs. kN
   Wall Thickness Inches mm
  Maximum Working Pressure psi bars
  Maximum End Load Lbs. kN
    0.058 250
1,5 17,2
0.065 250
1,7 17,2
0.072 250
1,8 17,2
0.095 250
2,4 17,2
890
3.96
1,350
6.01
1,415
6.30
3,340
14.86
4,125
18.36
5,890
26.21
0.058 100
1,335
      1.5 6,9 5.94
  5 0.109 200 125 2,8 13,8
6 0.122 200 150 3,1 13,8
8 0.170 200 200 4,3 13,8
Notes:
0.072 100
2,060
1.8 6,9 9.17
  0.083 100
2,945
2.1 6,9 13.10
  10,370 0.109 100 5,180
46.10 2.8 6,9 23.0
  • For a one-time field-test only, the Maximum Joint Working Pressure may be increased to 1-1/2 times the Maximum Pressure column shown in the dimensional tables. For any parts installed in accor- dance with Bureau Veritas rules and regulations, this test is required.
• Pressure performance values shown for GRINNELL couplings on copper tubing are dependent on the use of the required copper roll sets for roll grooved copper tubing.
• Refer to Technical Data Sheet G510 Figure 672 Rigid Coupling - CTS.