 376 PRESSURE & DESIGN DATA Pressure Performance for Stainless Steel Pipe
ANSI 304/316 Stainless Steel Pipe
(4 of 4)
Maximum Pressure Rating psi
bar
   Nominal Pipe Size
Nominal Wall Inches
Pipe* Sch.
5 0.188 — — — — —
20 20.000 10 0.218 — — — 35 150 500 508,0 5,54 2,4 10,3
40 0.375 — — — — —
  ANSI
Inches Inches
DN mm
O.D.
mm Figure Figure Figure Figure Figure 405 472 705 707 772
   4,78
        9,53
    5 0.218 — — — — —
5,54
    24 24.000 10 0.250 — — — 200 200 600 609,6 6,35 13,8 13,8
40 0.375 — — — — —
Notes:
• For parts installed in accordance with Bureau Veritas rules and regulations, a one-time only field-test is required to a maximum joint working pressure to 1-1/2 times the rated pressure shown in the Max. Pressure column of the dimensional tables for the following Figures: 71, 201, 210, 219, 260, 301, 303, 311, 312, 321,327, 341, 350, 522, 705, 707, 716, 730, 772, and 774. This test is in accordance with
BV NR 467, Pt. C, Ch. 1, Sec. 10, [20.4.2.], where applicable. Tests are to be attended by a local BV
Surveyor.
• Pressure performance values shown for GRINNELL couplings on light-wall
(Sch. 5 & Sch. 10) stainless pipe are dependent on the use of the required special rolls for roll groov-
ing light-wall stainless pipe.
• Refer to Technical Data Sheets G810, G820, and G830 for more information.
    9,53
     