Page 242 - Mechanical Products Installation Handbook IH-1000M
P. 242

 234 MECHANICAL TEES & CROSSES Figure 730 Mechanical Outlet Loss
(3of3)
as Equivalent Pipe Length
 Nominal Size Run x Branch ANSI Inches / DN
165,1mm x 76,1mm* (DN150 x DN65)
165,1mm x 4 (DN150 x DN100)
8 x 2-1/2 (DN200 x DN65)
Equivalent Length of Schedule 40 Steel Pipe
Feet (Meters)
Figure 730 Figure 730
 Threaded
Grooved
11 (3,35)
14 (4,27)
10 (3,05)
9 (2,74)
5 (1,52)
11 (3,35)
14 (4,27)
 165,1mm x 2-1/2 (DN150 x DN65)
  10 (3,05)
   165,1mm x 3 (DN150 x DN80)
  9 (2,74)
  8 x 2 (DN200 x DN65)
  5 (1,52)
  8 x 76,1mm* (DN200 x DN65)
  11 (3,35)
 8 x 3 (DN200 x DN80) N/A
216,3mm X 2 (200 JIS x DN50)
216,3mm X 76,1mm* (200 JIS x DN65)
216,3mm X 4 (200 JIS x DN100) N/A
 8 x 4 (DN200 x DN100)
  N/A
  14 (4,27)
  216,3mm X 2-1/2 (200 JIS x DN65)
  10 (3,05)
  216,3mm X 3 (200 JIS x DN80)
  N/A
  9 (2,74)
  •
Refer to Technical Data Sheet G210 Mechanical Outlet Tees and Crosses, Threaded/Grooved.


























































   240   241   242   243   244